Application: RTD measuring temperature use the priciple that the resistance of conductor semiconductor change according to the temperature. Its measuring range from -200~600¡æ. Its advantages are extreme accuracy. And it can send 4-20mA signal. Usually measure the low or medium temperature.
Material of the protect tube: 1Cr18Ni9Ti
Graduation: PT100 or PT10 or Cu50 or Cu100
Measuring range: -200~600¡æ (PT100 or PT10); -50~150¡æ (Cu50 or Cu100)
Tolerance deviation ¡÷t (¡æ): PT100 or PT10: A¡À(0.15+0.002 |t|), B¡À(0.30+0.005 |t|) Cu50 or Cu100: ¡À(0.30+0.006 |t|)
Min.insert length: 100mm
|